4.(a) Using Worksheet, sketch how an a.c. motor would be connected in EACH of the following:
(i) Star;(3)
(ii) Delta.(3)
(b) State the probable consequences of connecting a motor in star instead of delta.(4)
Question 3.
Although all can show a triangle and star shape many are unable to transfer this to a terminal box layout. Few consider the effect on the distribution system od a large motor starting.
How an a.c. motor would be connected in Star
To connect a three-phase AC motor in a star (or wye) configuration, you’ll work with the six terminals typically found in the motor’s terminal box. Here’s how:
1. Terminal Identification:
- The six terminals will usually be labeled U1, U2, V1, V2, W1, and W2.
- These correspond to the start and end points of each of the three motor windings:
- U1 & U2: Winding 1
- V1 & V2: Winding 2
- W1 & W2: Winding 3
2. Making the Star Connection:
- Join the Ends: Connect the three “end” terminals together (U2, V2, W2). This common point is the “star point” or “neutral.”
- Leave Starts Open: The “start” terminals (U1, V1, W1) remain separate.
3. Connecting to Power:
- Three Phases: Each of the three power supply lines (L1, L2, L3) is connected to one of the “start” terminals (U1, V1, W1).
- Neutral (Optional): If the motor’s application requires a neutral connection, a fourth wire (N) is connected to the star point.
Key Points to Remember:
- Reduced Voltage: In a star connection, the voltage across each individual winding is lower than the line voltage (by a factor of 1/√3, approximately 58%).
- Lower Starting Current: This reduced voltage results in lower starting current, which is often desirable for large motors to avoid stressing the electrical system.
- Lower Starting Torque: However, the starting torque is also reduced proportionally, so it might not be suitable for all applications.
- Neutral Availability: The star point provides a neutral connection if needed.
- Motor Nameplate: Always consult the motor’s nameplate for the correct voltage ratings and connection diagrams.
Safety First:
Proper Tools and PPE: Use insulated tools and appropriate personal protective equipment.
Qualified Personnel: Only qualified electricians should perform motor connections.
Disconnect Power: Ensure power is completely isolated before working on the terminal box.
How an a.c. motor would be connected in Delta
To connect a three-phase AC motor in a delta (Δ) configuration, you’ll again work with the six terminals in the motor’s terminal box. Here’s how:
1. Terminal Identification:
- Same as in star connection, the six terminals are labeled U1, U2, V1, V2, W1, and W2, representing the start and end points of the three windings.
2. Making the Delta Connection:
- Connect End to Start: Connect the end of each winding to the start of the next, forming a closed triangle:
- U2 connects to V1
- V2 connects to W1
- W2 connects to U1
3. Connecting to Power:
- Phases to Junctions: The three power supply lines (L1, L2, L3) are connected to the three junctions (corners) where the windings are joined:
- L1 to the junction of U1 and W2
- L2 to the junction of U2 and V1
- L3 to the junction of V2 and W1
Key Points to Remember:
- Full Line Voltage: In a delta connection, each winding receives the full line voltage, leading to higher current and torque compared to a star connection.
- Higher Starting Current: This configuration draws a higher starting current, which can be a consideration for the power supply system.
- Higher Starting Torque: The motor produces higher starting torque, making it suitable for applications with heavy starting loads.
- No Neutral: There’s no neutral point in a delta connection.
Safety First:
- Qualified Personnel: Motor connections should only be performed by qualified electricians.
- Power Isolation: Ensure power is fully disconnected before working on the terminal box.
- Motor Suitability: The motor must be designed for delta connection, with the correct voltage rating indicated on its nameplate.
Remember: If unsure about any aspect of the motor connection, always refer to the manufacturer’s documentation or consult a qualified electrician to ensure safe and proper installation.
Probable consequences of connecting a motor in star instead of delta
Connecting a motor designed for delta operation in a star configuration will have several consequences, primarily related to reduced voltage and current across the windings:
- Reduced Power and Torque:
- Each winding in a star configuration receives only 1/√3 (approximately 58%) of the line voltage compared to a delta connection.
- This results in a significant reduction in the motor’s power output and torque capability, typically to about 1/3 of its rated values.
- The motor may struggle to start or operate under load, especially if the application demands high starting or full-load torque.
- Overheating and Potential Damage:
- The reduced voltage in star connection can lead to the motor drawing a higher current than its design rating to compensate for the lower power output.
- This excessive current flow can generate significant heat in the motor windings, potentially causing overheating, insulation breakdown, and ultimately motor damage or failure.
- Reduced Speed:
- The motor’s speed is also affected by the reduced voltage in the star configuration.
- It will run at a lower speed than its rated speed in delta connection, impacting the performance of the driven equipment or process.
- Tripping of Overload Protection:
- If the motor’s overload protection is set for delta operation, it might not trip quickly enough to protect the motor from the excessive current drawn in star configuration.
- This can further increase the risk of overheating and damage.
- Operational Inefficiency:
- The motor will operate inefficiently in star mode, drawing more current than necessary for the reduced power output. This can lead to increased energy consumption and higher operating costs.
Additional Considerations:
- The severity of the consequences depends on the specific motor design, its load characteristics, and the duration of operation in star configuration.
- Short-term operation in star mode for starting purposes might be acceptable for some motors, but prolonged operation can lead to serious damage.
- It’s crucial to consult the motor’s nameplate and technical documentation to ensure it’s suitable for star connection and to understand any specific limitations or precautions.
Conclusion:
Connecting a motor designed for delta operation in star configuration is generally not recommended, as it can lead to reduced power and torque, overheating, potential damage, and operational inefficiency. It’s essential to ensure the correct connection configuration based on the motor’s design and application requirements to avoid these negative consequences.