Aux 2 Unit 8 Refrigeration General overview Q3 Answer

4.(a) State THREE reasons for the operation of a High Pressure Cut-out in a vapour compression refrigeration system.(3)
(b) Describe the operation of the High Pressure Cut-Out, employed in a vapour compression refrigeration system shown in the figure.

(a) THREE reasons for the operation of a High Pressure Cut-out in a vapour compression refrigeration system (3 marks)

The High Pressure Cut-out protects the system against excessive condenser/discharge pressure. It may operate due to:

  1. Failure or loss of condenser cooling medium (e.g. seawater flow failure, air-cooled condenser fan failure).
  2. Overcharge of refrigerant → too much liquid in the condenser raising pressure.
  3. Blocked or fouled condenser tubes → reduced heat transfer surface, causing pressure build-up.

(b) Operation of the High Pressure Cut-Out (7 marks)

Principle of operation (based on the figure):

  • The cut-out is a pressure-actuated switch connected to the compressor discharge line.
  • Diaphragm/Bellows element:
    • Discharge gas pressure acts on the diaphragm/bellows.
    • Opposed by a pre-set calibrated spring force (set to the maximum safe pressure).
  • Normal operation:
    • Pressure remains below the set limit → spring holds contacts in the closed position, allowing compressor motor to run.
  • Overpressure condition:
    • When discharge pressure rises above the set point, the force on the diaphragm overcomes the spring.
    • This movement operates a toggle linkage that trips the electrical contacts.
    • Contacts open → compressor motor is stopped, preventing damage.
  • Reset:
    • Typically requires manual reset (push-button) to restart, ensuring the engineer checks the fault before recommissioning.